Overview
All NRL/RTU units routinely collect and log sensor data. NRLs then periodically connect to a central Neon comms and web server via an IP network and use a push data model to upload the logged data. The central Neon server can be cloud-hosted, virtual, or physical. The Neon server is offered as a Neon data-hosted service using a Unidata Neon server for a monthly fee. Otherwise, customers can purchase a Neon server license and run the Neon software on their own server. The Neon system receives, processes, displays, stores, and reports collected data in many ways. The Neon system also can issue control commands based on pre-set algorithms and issue alarms/notifications via several mediums. Alarm set-points can be set up on the NRL/RTU unit itself as well as on the Neon central server. The alarm notifications can be sent via several methods, including email and SMS text messages.
Alarm triggers can initiate physical actions in the field, such as turning pumps on and off r activating other control functions based on the internal program within the NRL/RTU. The Neon system has fully bi-directional communications between the NRL/RTU units and the central Neon server. This allows for remote diagnosis, remote programming and remote firmware updating for the operation of the remote equipment, thereby reducing costly site visits. NRL/RTU units can be configured to read sensors, log data internally to local memory and push data to the central Neon server at user-settable intervals such as once a minute, every few minutes, every hour, or once a day. Data is to be viewed on the Neon Web server in near real-time from any browser and can be reported to other systems using email, FTP, and web services.
Specifications 3004N

Integrated logger specifications
- Storage memory: 7.5Mbytes Flash (non-volatile), 3.75 Million log data points
- Scan rate: Programmable from 1 second to 5 minutes
- Log rate: Programmable from 1 second to 24 hours
- Time clock: Battery Backed Real Time Clock (RTC), Accuracy +/- 10 seconds/month (non-Neon version), locked to server time clock (Neon version)
- CPU: 16 Bit, 20MHz, Ultra-Low Power
Electrical specifications
- External Power 9 to 30V DC
- Current Draw: 50µA Standby, Max 500mA Active
- RTC Backup Battery: 3.6V Li Coin Cell (5-year life)
- Internal Power: 3.6 Volt Lithium D Cell
- Instrument Power: 5.5V (100mA) to 18V (60mA) regulated, 80mA user programmable
- Instrument Reference Voltage: 2.5V 10mA Max
- Analog channels: 4, Single-ended (max) or 2 Differential (max), 24-bit resolution, 4 user-selectable gain ranges: 0 to 5V (gain = 1) 0 to 1.25V (gain = 4) 0 to 312.5mV (gain = 16) to 0 to 39.0625mV (gain = 128)
Physical specifications
- Material: Powder Coated Aluminium Enclosure
- Size: 108mm x 97mm x 81mm (LxWxH), 330g
- Operating Temperature: -20° to +60°C. Not affected by humidity
- Antennae: Model dependant, external stub/whip/satellite antenna
- Modbus: 1 independent channel, RS485, RTU or ASCII protocol, 57600 baud (max), functions 01, 02, 03, 04, 05/15, 06/16
- SDI-12: 1 independent channel, SDI interface, 16 channels, bi-directional
-
Counters: 4,
2 x 16 bit, DC to 20kHz potential free contacts or 0 to 5V DC digital input (C0,C2); 2 x 16 bit, dc to 300Hz potential free contacts or 0 to 5V DC digital input (C1,C3) - Unidata HSIO: High-speed serial interface, 16 channels, bi-directional
- Digital Outputs: 1 Open Drain FET, 30V DC, 250mA max
- Configuration Port: USB B Micro Port and SD Micro Card
-
Modem Options:
– Cellular 3G/4G/LTE Dual SIM support
– NBIoT
– Satellite Iridium SBD - Accelerometer: Senses changes in logger orientation
- Barometer: 260-1260hPa Absolute Digital Output – Optional
- Bluetooth: Optional
Ordering Information
Model
Description
3004N-M1 B L M2
N Series Neon Remote Logger
M1 - Options
0
Standalone
C
Cellular 3G/4G/LTE
N
NBIoT
S
Iridium SBD
B - Options
0
No Battery
D
Cell Lithium Battery
LCD - Options
0
No LCD
L
With LCD
M2 - Options
0
None
3110A
NRL FTS
Documents
Application Notes
Agricultural
Environmental
Industrial
- Cell tower monitoring
- Geothermal power station monitoring
- High voltage transmission tower monitoring
- Industrial outflow monitoring
- Industrial tank level monitoring
- Oil & gas pipelines / pressure monitoring and metering
- Oil Beam pump and esp pump monitoring
- Pipeline cathodic protection
- Ports and harbours monitoring
- Power utility remote recloser system