Home Product Catalogue Neon & IP Loggers News & Brochures Product Support Where to Buy Connect To Our FTP Contact Us By Phone Contact Us By Email Staff Portal

Product Support

Product Alert #17

STARLOGGER DATA LOGGER - Model 6004B - Serial #751 onwards - V22.2

Starlogger Issues

21 June 1994

17.1 Firmware Version 22.2 – Delta based EVENT Logging continuously logs data

Problem

The JMPGT/JMPLE instruction operates incorrectly when the “src” operand contains zero.

Symptom

A Delta EVENT based logging scheme uses the JMPLE instruction to determine if a change has occurred. However, if the change value is zero (no change) then logging occurs, when no logging is expected.

17.2 Sense 1 not stored in B32 (Model 6004B)

Problem

The STARLOGGER does not store the status of the Sense 1 input into B32 register.

(Note: Sense 1 is also used for SDI-12 data communication and is normally low and must be pulled high to 5V (pin 13) to activate instead of shorting to ground (as in the Model 6004A). However, when using a potential free contact, the B32 result will be the same as in the Model 6004A.)

Correction

Upgrade the Model 6004B STARLOGGER to V22.3 Firmware.