Product Alert #16
STARLOGGER DATA LOGGER - Model 6004A/B - Serial #s 301 to 750
Starlogger Issues
11 May 1994
16.1 V21.10/V22.1 Firmware Error – 1st count lost after loading scheme (Model 6004A)
Problem
After a scheme is loaded into a Model 6004A with V21.9 firmware, the first count into each counter channel will not be registered.
Note: This problem had been previoulsy corrected and was re- introduced in V21.9.
Correction
Upgrade the Model 6004A STARLOGGER to V21.11 Firmware.
16.2 Improved HSIO Compatibility in 6003 Mode (Model 6004A/B)
Problem
The STARLOGGER will recognise HSIO Clock selection from B10 of the Register Block. This enables Clock 1 to be used used with Data 0 (and Clock 0 with Data 1) in SERIN & SEROUT instructions.
There is no change to 6004 mode operation.
Correction
Upgrade the STARLOGGER to V21.11 Firmware (Model 6004A) or V22.2 Firmware (Model 6004B).
|